Occupant load factor >Amount of floor area presumed to be occupied by one person >Based on generic function of building spaces Gross floor area >Includes stairs, corridors, toilet rooms, mechanical rooms, closets, and interior partition thicknesses Net floor area >Includes space that is actually used Required number of exits or exit access doorways determined by several factors: 1. Because of the additional time it may take to evacuate a building or part of a building where the means of escape is based on vertical phased evacuation, the following fire safety measures should be provided: installation of an automatic fire detection and alarm system to BS 5839: Part 1: 2017, Category L2, and, a voice alarm should be installed in accordance with BS 5839: Part 8: 2013. The minimum lateral load that fire walls are required to resist is five pounds per square foot. Locks on exits doors or locks on doors across escape routes present difficulties when assessing the need for security against the need to allow safe egress from a building in the event of a fire. Type of Building Type of Room Area per Person (m 2) (ft 2) Apartments: 100 - 400: Assembly building: . For this example it is assumed that every storey is a compartment storey and that the occupants are distributed evenly across each storey, therefore the number of occupants will be split evenly to each escape stair. However the floor of the lowest storey or an external wall (other than an external wall described in clause 2.9.36) need not be fire resistant. Where the escape stair serves only one storey, the appropriate capacity equals the occupancy capacity of the storey served by the escape stair (see diagram below). The walls/doors separating the toilets or washrooms from the protected zone need not have a fire resistance duration. Instead, the calculated occupant load is actually the . Ventilation may be provided by means of mechanical extract ventilation or by natural ventilation direct to the external air, additional guidance is provided in BS 5588: Part 6: 1991. Therefore, escape routes over flat roofs should only be used where the building or part of the building is inaccessible to the general public and there is more than 1 escape route from the room or storey leading to the flat roof. Some electric locking devices fail locked on both sides of the door when electrical power is withdrawn and does not give mechanical escape by panic bar, handle or push pad. November 2020 The lobby is designed to accommodate 3 sq. A layout, which only follows the recommendations for travel distance and number of storey exits, may still result in an undesirable layout. The number of escape routes from a room or storey exits relates to: the use and occupancy profile within the building, the height of a storey above the ground or the depth below ground, and. All of them have exits through spaces other than the lobby. Any door openings in the proscenium wall other than the proscenium opening should be provided with protected lobbies with short fire resistance duration. Every wall not more than 2m from either side of the escape route, should have a short fire resistance duration up to a height of at least 1.1m measured from the level of the escape route. For this example it is assumed that the occupants are distributed evenly across each storey, therefore the number of occupants will be split evenly to each escape stair. Extract ventilation should preferably be taken from high level positions to assist in keeping the main auditorium clear of smoke. (2) If a floor area or part of it has been designed for an occupant load other than that determined from Table 3.1.17.1., a permanent sign indicating that occupant load shall be posted in a conspicuous location. The number generated does not reflect an official occupant load. We don't save this data. Travel distance is the distance measured along the actual route of escape from any point within a storey to the nearest protected door giving direct access to: to a door in a sub-compartment wall as described in annex 2.A and annex 2.B. Example 2 The same hall, as in example 1, is 16m long by 9m wide and a school intends holding a disco, without any tables, chairs etc. Products The methodology for calculating the appropriate capacity must also take into account whether a building has been based on simultaneous or phased evacuation. Occupant load is defined as the maximum probable number of occupants expected to inhabit a building or space [3-5]. However an escape route may pass through a wider circulation area leading to a narrower circulation area provided the latter is of a width at least that recommended for the escape route. In buildings with 2 or more protected zones, the occupants have an alternative route out of the building if one of the protected zones was affected by fire or smoke. The aggregate unobstructed width in mm of all escape routes from a room, or storey, should be at least 5.3 x the occupancy capacity of the room or storey. The risk to occupants is greater if they are asleep during the outbreak of fire as their ability to detect a fire and to escape will be greatly impaired. Now before we run into an example of how to calculate the occupant load based off this table, I want to point out two important factors. See annex 2.A for additional guidance on residential care buildings and annex 2.B for hospitals. See table below for occupant load factors. The plan checker wants to assign a 15 SF/occ load on the entry lobby, and because there is no door at the hallway, he is also assigning the lobby occupant load into the hallway space itself. Is that true even when a Major Vertical Penetration is next to an exterior building wall? This table describes the occupant load factor based on the function of the space. To ensure the safe and smooth movement of occupants and prevent unnecessary increase in anxiety during an evacuation the following should not be part of an escape route: a turnstile, other than a suitably designed and installed turnstile unit with an emergency break out facility enabling the entire unit to open in the direction of escape, or, any shutter; other than one which is installed for security purposes across a shop front and which does not close automatically in the event of fire, or. (Applicable to all BOMA Floor Area Measurement Standards), BOMA Best Practice #13- How many decimal places do I need to carry in my calculations in order to comply with the BOMA floor area measurement standards? An escape route and circulation area should have a clear headroom of at least 2m. where the occupancy capacity of a room is not more than 100, the room exits may give access to the same space provided the guidance for alternative directions of escape has been followed. If further evacuation is required this is done on the basis of the next two adjoining upper storeys to avoid congestion in the escape stairs. ", Joe Meyer, PE, is a Fire Protection Engineer out of St. Louis, Missouri who writes & develops resources for Fire Protection Professionals. The accommodation within every protected zone should be limited to places where fire is unlikely to start. 6360 However if the door is an emergency door or a door serving a place of special fire risk, the side-hung door should open in the direction of escape regardless of occupancy levels. EW = {5.3 x 360} over {2 - 1}, = 360 a wall or screen with a short fire resistance duration for integrity is provided between the opening and the route of escape. This type of fail unlocked electric locking device should unlock instantly when electrical power is withdrawn and should unlock even when pressure is being applied to the escape door by occupants trying to escape at the time that electrical power is withdrawn. These are devices that require electrical power to be withdrawn from them to unlock. The escape routes on the ground storey do not communicate with the escape stairs. The evacuation time from a room or storey is controlled by the number of exits and the time taken for occupants to pass through the exits. This material is COPYRIGHT QUEEN'S PRINTER FOR ONTARIO, 2008-2018. The system should be balanced to ensure that the forces required to open doors are not greater than those specified in Section 4 Safety. Do you actually have tables and chairs in the lobby? This type of locking device is released mechanically by a single action applied to the door lever handle or push pad to allow people familiar with the building to escape in an emergency. A reception room, an office and a general store room, each of not more than 10m2 may be located within the protected zone as they are of limited size and the potential fire load is low. For more detailed guidance refer to BS 5588: Part 9: 1999. November 2019 We previously discussed that the Building Official has the authority to permit an occupant load that is less than the actual number calculated in limited unique circumstances, however the Building Official also has the authority to permit a greater occupant load than calculated. (Applicable to ANSI/BOMA Z65.1-2017), Any questions? This does not mean that the corridor should be subdivided into 12m lengths. The guideline for determining usage intensity numbers is found . Calculators However where the building has limited occupancy numbers the escape stair width may be reduced as follows: 1100mm where the number of occupants using the stair is not more than 225, and. The gross floor area shall not include shafts with no openings or interior courts.. The code recognizes this and has 2 factors to use. = For additional guidance on hospitals, see annex 2.B. Therefore, a protected lobby need not be provided where the building: is a non-residential building with no more than 300 occupants, and, no storey is at a height of more than 7.5m, and. Revolving doors and automatic doors can obstruct the passage of persons escaping. Occupant load The occupant load shall be based on the floor area of the temporary workers' quarters on the basis of 6m 2 per person, excluding non-simultaneous areas such as toilets, kitchens etc., or the actual number of occupants for which each occupied space of the floor is designed as shown on the plan, whichever is greater. The maximum permitted occupant load of a given space shall be determined by dividing the floor area for a given use by the occupant load factor in Table 5:70-4.11(f)3. i. When this table is used, it results in an occupant load for which a room, space and building is designed to. It is important that ducted heating and ventilation systems including air conditioning systems, installed to maintain interior environment conditions, that serve the building should not transfer fire and smoke to or from; any compartment to any other compartment, escape route, common space, roof space or other concealed space. Occupant load: Control vestibules are typically used in locations with a low occupant load, such as a laboratory clean room. October 2018 Estimate the net floor area by referring to the office blueprint. Therefore, there is no need to deduct 1 stair from the calculations: AC is the appropriate capacity of each of the 2 adjacent upper storeys, with the greater occupancy capacity, minus 20% for standing capacity in each of the stairs: EW In the event of a fire, there is always a risk that an opening in a floor could result in a proportion of fire or smoke and toxic fumes arising from a fire flowing up through the opening leading to a build-up of smoke on the upper storeys. Occupant load : Capacity of Exits : Exit width required : Total exit width required : 'redundancy' calculation : UBBL 168, 175, 176, 177, 181 Exit capacity calculation : Basement carpark Gross floor area = 40 000, assume 2 pax/car and 40m2/car, therefore 40 000/40 = 1000 car or 2000 pax/floor Compare 2000 to 6000 (shopping), factor reduction = 1/3 55 000 / 3 = 18300 mm . May 2020 They present additional hazards to occupants evacuating a building in the event of fire. December 2019 Although this exception is there it is best to understand its intent. Where a cavity extends across any of the self closing fire doors identified above, or above the walls described in clause 2.9.12 a cavity barrier with at least short fire resistance duration should be fitted above the sub-dividing wall and fire door to inhibit fire and smoke spread. The designer should consider detailing at junctions to inhibit fire and smoke spread into the protected route of escape. on activation of a manual door release unit (Type A) to BS EN 54: Part 11: 2001 they are connected to, positioned at the door on the side approached by occupants making their escape and where the door provides escape in either direction, a unit should be installed on both sides of the door. There are 100 occupants on the top storey, 150 occupants on the 2nd storey and 200 occupants on the 1st storey. In a building containing an auditorium, a ventilation system should be provided above all stages so that in the event of fire the occupants can escape before being overcome by the effects of fire or smoke. (Applicable to ANSI/BOMA Z65.1-2010), BOMA Best Practice #5- Can the load factor that is calculated in the BOMA Global Summary of Areas spreadsheet (load factor A or load factor B, if using Method B) be arbitrarily increased to bring it up to the "Market Factor"? Room exits to storey exits - where a room is located on a storey, which, due to the occupancy capacity, height of the storey or travel distance, is recommended to have 2 or more storey exits, the escape routes from the room exits to the storey exits should be designed as follows: where only 1 room exit is provided, the escape route from the room should lead to 2 independent storey exits. However, if one then places very large furniture in that area, the remaining open/available area may no longer be sufficient to accommodate the calculated occupant load even at 5 sfp. In chapter 10 the occupant load is used to design the means of egress system however other chapters of the code can use this number to determine other required features within a building or structure. You can target the Engineering ToolBox by using AdWords Managed Placements. 1 Assembly Areas, Less Concentrated Use (conference . 36 SF is an increase of 80%. Width of escape stairs is covered in clause 2.9.31. Each portion of a building must be based on the occupancy of that space. 300 gross. Occupancy capacity in rooms and spaces without fixed seating. K-12 are Educational College and University occupancies can be Assembly, or Business NFPA 101 2018 14.1.1.4 Educational facilities that do not meet the definition of an educational occupancy shall not be required to comply with this chapter but shall comply with the following requirements: (1) Instructional building business occupancy (2) Classrooms under 50 persons business occupancy . When you are designing restaurants, bars, bakeries and other food service businesses the number of occupants is a fairly important factor. The Gross Floor Area is defined by the 2018 International Building Code as: The clear opening width at doorways is measured in accordance with the diagram below: Figure2.7. The area in front of and around stages or . Oil and liquefied petroleum gas can produce pool fires, i.e. x any load calculation is to establish the design criteria for the project that involves consideration of the building concept, construction materials, occupancy patterns, density, office equipment, lighting levels, comfort ranges, ventilations and . Minimum number of storey exits. on any door accessible to the general public where the aggregate occupancy capacity of the rooms or storeys served by the door exceeds 60 persons. (a) the number of seats in an assembly occupancy having fixed seats, (b) two persons per sleeping room or sleeping area in a dwelling unit or suite, or. The design occupant load determines the means of egress requirements therefore establishing the correct occupant load is important. Applicable to ANSI/BOMA Z65.1-2010), BOMA Best Practice #3- Purpose: to provide a consistent, detailed method of allocating inter-building service and amenity areas among different buildings that they serve in a multi-building set in accordance with general direction included in the BOMA 2010 Office Standard. July 2019 The building standards technical handbooks provide guidance on achieving the standards set in the Building (Scotland) Regulations 2004. More than one storey example. Standpipes Divide by the occupant load . December 2022 Calculation of effective width - based on the above principles for simultaneous and phased evacuation, the effective width of every escape stair in mm can be calculated by the following formula: EW To calculate the occupant load for an area without fixed seating, the code says to compute the area of the room or space at a rate of one occupant per unit of area using the occupant load factor found in Table 1004.1.2. Only emails and answers are saved in our archive. It is an very-low-income apartment building for seniors at risk of homelessness (mostly vets). Does this apply to service elevator lobbies and secured elevator lobbies as well? It may also include exterior covered spaces that are part of the building's occupiable space. . The lobby will be an Assembly Use group (A-2) and the guestrooms will be a Residential use group (R-1). Requirements for maximum capacity signs (sometimes called "occupancy placards") have been streamlined and clarified. In determining means of egress requirements, the number of occupants for whom means of egress facilities are provided shall be determined in accordance with this section. All rights reserved. = However it is important to remember that the guidance in the annexes is in addition and supplementary to the guidance to Standard 2.1 to 2.15. It is based on the 2018 IBC. Premises that offers table games along with other activities, such as arcade games or slot machines. = (3) For the purposes of this Article, mezzanines, tiers and balconies shall be regarded as part of the floor area. Method of measuring seatway widths, Table2.14. The travel distance should allow for the occupants to reach a protected door before being overcome by fire or smoke. where the corridor provides at least 2 directions of escape and is more than 12m in length between the exits it serves, it should be divided in the middle third of the corridor.